Switching Sink / Source NPN / PNP On TM Control Box
更新日 2026 / 03 / 03
Examples are valid for:
TMflow Software version: All
TM Robot Hardware version: HW 3.2 or above
Other specific requirements: None
Note that older or newer software versions may have different results.
Set to Sink Input Type
When a device such as a transistor output sensor is connected, NPN open collector transistor output can be used.

Set to Sink Output Type
Connect DO_COM terminal to the minus side of the power supply.

Set to Source Input Type
When a device such as a transistor output sensor is connected, PNP open collector transistor output can be used.

Set to Source Output Type
Connect DO_COM terminal to the plus side of the power supply.